Your privacy is very important for us. When you visit our website, please agree to the use of all cookies. For more information about the processing of personal data, please go to Privacy Policy

  • HI5KTHcemian11.png
  • HI5KTHxiliezhengmian11.png
  • HI5KTHdibutu.png
Hybrid Inverters

HI-5~12K-TH

  • 5~12kW
  • Three Phase
  • High Voltage

Technical Parameters

Inhenergy HI-5-12K-TH SERIES inverter, ranging from 5-12kw, weight only 20kg. It is compatible with high voltage Li-Ion batteries ranging from 150 to 600V. Support generator interface to meet a variety of usage needs. Support up to six inverters connected in parallel, with a maximum output power of 72kw.


  • fuyong2-849.png

    Core Value
    Future proof battery ready
    Low initial investment

  • fuyong1-67.png

    High Yields
    DC/AC ratio up to 1.5
    Max. efficiency 98%

  • gongsijieshaoyoushishuju6.png

    Safety and Reliability
    Type II SPD on DC side
    Support export limitation

  • 65-277.png

    Leading Functions
    UPS function, 10ms transition
    Smart Meter Integrated

  • dianchi-236.png

    System Flexibility
    Support lithium and lead-acid battery
    Whole home backup

  • gongsijieshaoyoushishujuTop3-810.png

    Support GEN

Technical Data
Technical DataHI-5K-THHI-6K-THHI-8K-THHI-10K-THHI-12K-TH
PV String Input Data




Max. DC input power7500W9000W12000W15000W18000W
Max. DC input voltage

1100V

Nominal input voltage

600V

MPPT working voltage range

180V-1000V

Number of independent  MPPT / strings per MPPT

2/1+1

MPPT max. current

20A/20A

Start-up voltage/Min.operating voltage

200V/180V

AC Output/Input Data (On-grid)




Nominal output apparent power5000W6000W8000W10000W12000W
Max. output apparent power5500VA6600VA8800VA11000VA13200VA
Nominal output voltage

400V±20%

Nominal ouput freqency

50Hz,60Hz/±5Hz

Max. output current8A10A13A16A19A
Power factor

-0.8~+0.8(adjustable)

THDi

<3%(Nominal Output)

Grid system pattern

3L+N+PE

Max.apparent power from utility grid11000VA12000VA16000VA20000VA24000VA
Max.AC current from utility grid16A20A26A32A40A
Back-up Output Data (UPS)




Peak output apparent power5500VA,10s6600VA,10s8800VA,10s11000VA,10s13200VA,10s
Nominal output apparent power5000VA6000VA8000VA10000VA12000VA
Nominal output voltage

400V±20%

Nominal ouput frequency

50Hz/60Hz

Output THDV

<3%

Automatic switch time

<20ms

Battery Input Data




Battery type

Li-Ion

Battery voltage range

150V-600V

Max. charging/discharging current25A25A25A25A25A
Battery capacity(AH)

50-2000

Charging strategy for Li-Ion battery

Self-adaption to BMS

Eciency




Max. effificiency98%98%98%98%98%
Europe effificiency97.5%97.5%97.5%97.5%97.5%
Max. battery to load effificiency98%98%98%98%98%
Protection




Anti islanding protection

Yes

Insulation impedance protection

Yes

RCD detection

Yes

PV reverse polarity protection

Yes

Output over voltage protection

Yes

Output over current protection

Yes

General Data




Dimensions(W/L/H)in mm

403/465/285

Weight

20kg 

Operation temperature range

-25℃~+60℃

Heat dissipation mode

Natural

IP Class

IP 65

Maximum altitude

4000m

Self-Consumption night

<3w

Topology

Transformerless

Features




LCD display

Yes

Communication interface

WiFi/4G/USB/CAN/RS485

Standards

EN 62109-1/EN 62109-2/EN 62477-1/IEC 61000-6-1/IEC 61000-6-3/ CEI 0-21/UNE 217001/UNE 217002/VDE 0126/IEC 61727/IEC 62116/ EN 50549-1/G98/G99/AS 4777.2